Part Number Hot Search : 
ZFMG14C 100100 16DIP SP701 144LU J110C AOZ1012 REF192
Product Description
Full Text Search
 

To Download ASD-PTL2F Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 Velociti(R) Series ASD-PL2F and ASD-PTL2F
Description
The Gamewell-FCI Velociti(R) Series, analog addressable plug-in smoke sensors with integral communication provide features that surpass conventional sensors. Sensitivity can be programmed in the control panel software, and is continuously monitored and reported to the panel. Point ID capability allows each sensor's address to be set, providing exact locations for selective maintenance when the chamber contamination reaches an unacceptable level. The ASD-PL2F photoelectric sensor's unique optical sensing chamber is engineered to sense smoke produced by a wide range of combustion sources. Dual electronic thermistors add 135F (57C) fixed-temperature thermal sensing on the ASD-PTL2F model. The Velociti(R) Series use a communication protocol that substantially increases the speed of communication between the sensors and certain Gamewell-FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel's microprocessor stops the group poll and concentrates on the single device. The net effect is a response speed up to five times greater than earlier designs.
Analog, Addressable Photoelectronic Smoke Sensor
ASD-PL2F
ASD-PTL2F
Features
* Sleek, low-profile design * Visual rotary, decimal switch addressing (01-159) * Built-in functional test switch activated by an external magnet * Bicolor LEDs flash green whenever the sensor is addressed, and light steady red on alarm* * Optional relay, isolator, or sounder bases * Low standby current * Analog addressable communication * Stable communication technique with noise immunity * Optional remote, single-gang LED Indicator (RA400Z) * Suitable for installation in ducts * Compatible with Gamewell-FCI analog addressable panels
Note: *Only the red LED is operative in panels that do not operate in Velociti(R) mode.
Ordering Information
Model Description ASD-PL2F Analog, addressable photoelectronic smoke sensor ASD-PTL2F Analog, addressable photoelectronic smoke sensor with thermal sensing
An ISO 9001-2000 Company
SIGNALING
Velociti(R) is a registered trademark of Honeywell International Inc. UL is a registered trademark of Underwriters Laboratories Inc.
(R)
S1913
FM
APPR OVED
Approved 3023594 219-02-E Vol.VI 07272-0694:263
MEA
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. www.gamewell-fci.com 9020-0617 Rev. E1 page 1 of 2 (c)2008 by Honeywell International Inc. All rights reserved.
12 Clintonville Road, Northford, CT 06472-1653 USA * Tel: (203) 484-7161 * Fax: (203) 484-7118
GAMEWELL-FCI
Installation
ASD-PL2F plug-in sensors use a separate base to simplify installation, service, and maintenance. A special tool allows maintenance personnel to plug-in and remove sensors without using a ladder. Mount the base on a box which is at least 1.5" (3.8 cm) deep. Suitable mounting base boxes include:
* 4.0" (10.2 cm) square box * 3.5" (8.9 cm) or 4.0" (10.2 cm) octagonal box * Single-gang box (except relay or isolator bases) * With B501BH or B501BHT base, use a 4.0" (10.2 cm) square box * With B224RB or B224BI base, use a 3.5" (8.9 cm) octagonal box, or a 4.0" (10.2 cm) octagonal or square box
Specifications
2.1" (5.1 cm) high x 4.1" (10.4 cm) diameter installed in B501 base, 6.1" (15.5 cm) diameter installed in ADB-FL base. Shipping Weight: 5.2 oz. (147 g) Operating Temperature: ASD-PL2F: 32 F to 120 F (0 C to 49 C) ASD-PTL2F: 32 F to 100 F (0 C to 38 C) Size: UL(R)-Listed Velocity Range: 0-4000 ft./min. (1,219.2 m/min.), suitable for installation in ducts.
Relative Humidity: 10-93% (non-condensing) Thermal Ratings: Fixed-temperature setpoint 135 F (57 C)
NOTE: Because of the inherent supervision provided by the SLC, end-of-line resistors are not required. Wiring "T-taps" or branches are permitted for Style 4 (Class "B") wiring. Sensor Spacing Gamewell-FCI recommends spacing sensors in compliance with NFPA 72. In low airflow applications with smooth ceilings, space sensors 30 feet (9.1 m). For specific information regarding sensor spacing, placement and special applications, refer to NFPA 72.
Electrical Specifications
VoltageRange: 15 - 32 volts DC peak Standby Current: (max. avg.): .0003 A @ 24 VDC (one communication every 5 seconds with LED enabled) Maximum Alarm Current: .0065 A @ 24 VDC (LED) lit).
Bases and Options
ADB-FL B501 B501BH or B501BHT B224RB Relay Base 6.1" (15.5 cm) diameter 4.1" (10.4 cm) diameter Sounder base assembly (B501BHT produces a temporal pattern). Includes B501 base Screw terminals: Up to 14 AWG (2.0 mm2) Relay type: Form-C Rating: 2.0A @ 30 VDC resistive; 0.3 A @ 110 VDC inductive; 1.0 A @ 30 VDC inductive. Dimensions: 6.2" x 1.2" (15.7 x 3.0 cm) Maximum: 25 devices between isolator bases. Remote alarm indicator, LED. Black detector covers (box of 10)
RA400Z BCK-200
12 Clintonville Road, Northford, CT 06472-1653 USA * Tel: (203) 484-7161 * Fax: (203) 484-7118 9020-0617 Rev. E page 2 of 2 www.gamewell-fci.com
GAMEWELL-FCI


▲Up To Search▲   

 
Price & Availability of ASD-PTL2F

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X